3NJ4103-3BF01 FUSE SWITCH DISCONNECTOR, SIZE 00
From SIEMENS
In-line fuse switch disconnector 3-pole selectable, Sz. 00 I=160 A, U=690 V AC Flat terminal M8 for cable lug 1x 10-95 mm2 | ||
Model | ||
Product brand name | SENTRON | |
Product designation | Fuse switch disconnectors | |
Design of the product | in in-line design | |
Design type | Fixed-mounted | |
Type of switching contact / double breaking switching contact | No | |
Design of the auxiliary release | No | |
Design of the auxiliary switch | No | |
Version of fuse monitoring | Without | |
Design of the load switch / Strip form | Yes | |
General technical data | ||
Number of poles | 3 | |
Number of poles / Note | 3-pole switchable | |
Type of device | For busbar system 185 mm | |
Size of fuse link | NH000, NH00 | |
Continuous current / at 35 °C / rated value | 160 A | |
cut-off value I**2t,max. / 500 V | 225 000 A²·s | |
circuit-breaker / Design | 3NJ4 | |
Fuse system | LV HRC fuse | |
Voltage | ||
Insulation voltage / rated value | 800 V | |
Protection class | ||
Protection class IP / on the front | IP30 | |
Dissipation | ||
Power loss [W] / for rated value of the current / at AC / in hot operating state / per pole | 6 W | |
Electricity | ||
Number of transformers | 0 | |
Continuous current | ||
rated value | 160 A | |
at 40 °C / rated value | 152 A | |
at 45 °C / rated value | 144 A | |
at 50 °C / rated value | 136 A | |
at 55 °C / rated value | 128 A | |
at 60 °C / rated value | 120 A | |
at 65 °C / rated value | 112 A | |
at 70 °C / rated value | 110.5 A | |
Let-through current / Ic / maximum permissible | ||
400 V | 15 kA | |
500V | 15 kA | |
cut-off value I**2t,max. / 400 V | 225 000 A²·s | |
Main circuit | ||
Operating voltage | ||
at AC / at 50/60 Hz / rated value | 690 V | |
at DC / rated value | 440 V | |
Operating current / with capacitive load | ||
at 400 V / maximum | 72 A | |
at 500 V / maximum | 55 A | |
Suitability | ||
Suitability for operation | System protection | |
Suitability for use | ||
Main switch | No | |
switch disconnector | Yes | |
EMERGENCY OFF switch | No | |
safety switch | No | |
maintenance/repair switch | No | |
Product details | ||
Product component | ||
Voltage trigger | No | |
undervoltage release | No | |
undervoltage release with leading contact | No | |
Short circuit | ||
Conditional rated short-circuit current / in utilization category | ||
AC-21 B / at 400 V | 50 kA | |
AC-21 B / at 500 V | 50 kA | |
AC-22 B / at 400 V | 50 kA | |
AC-22 B / at 500 V | 50 kA | |
Connections | ||
Arrangement of electrical connectors / for main current circuit | Screw terminal | |
Type of electrical connection / for main current circuit | screw-type terminals | |
Mechanical Design | ||
Height | 647 mm | |
Width | 49 mm | |
Depth | 150 mm | |
Mounting position | vertical | |
Mounting type | Flachanschluss, M 8 | |
Busbar center-to-center spacing | 185 mm | |
Busbar center-to-center spacing | ||
40 mm | No | |
50 mm | No | |
60 mm | No | |
100 mm | No | |
185 mm | Yes | |
Net weight | 2.18 kg | |
Environmental conditions | ||
Ambient temperature | ||
during operation / minimum | -25 °C | |
during operation / maximum | 55 °C |